HRTH跳位監(jiān)視、合位監(jiān)視、電源監(jiān)控繼電器
系列型號:
HRTH-Y-2H2D-X-T跳位監(jiān)視、合位監(jiān)視、電源監(jiān)控繼電器;
HRTH-Y-2Z-X-T跳位監(jiān)視、合位監(jiān)視、電源監(jiān)控繼電器;
HRTH-Y-2H-X-T跳位監(jiān)視、合位監(jiān)視、電源監(jiān)控繼電器;
HRTH-J-2H2D-X-T跳位監(jiān)視、合位監(jiān)視、電源監(jiān)控繼電器;
HRTH-J-2Z-X-T跳位監(jiān)視、合位監(jiān)視、電源監(jiān)控繼電器;
HRTH-J -2H-X-T跳位監(jiān)視、合位監(jiān)視、電源監(jiān)控繼電器;
HRTH-Y-2H2D跳位監(jiān)視、合位監(jiān)視、電源監(jiān)控繼電器;
HRTH-Y-2Z跳位監(jiān)視、合位監(jiān)視、電源監(jiān)控繼電器;
HRTH-Y-2H跳位監(jiān)視、合位監(jiān)視、電源監(jiān)控繼電器;
HRTH-J-2H2D跳位監(jiān)視、合位監(jiān)視、電源監(jiān)控繼電器;
HRTH-J-2Z跳位監(jiān)視、合位監(jiān)視、電源監(jiān)控繼電器;
HRTH-J -2H跳位監(jiān)視、合位監(jiān)視、電源監(jiān)控繼電器;
HRTH-2Z跳位監(jiān)視、合位監(jiān)視、電源監(jiān)控繼電器;
HRTH-2H2D跳位監(jiān)視、合位監(jiān)視、電源監(jiān)控繼電器;
HRTH-2Z-X-T跳位監(jiān)視、合位監(jiān)視、電源監(jiān)控繼電器;
HRTH-J-2H2D-X跳位監(jiān)視、合位監(jiān)視、電源監(jiān)控繼電器;
跳位、合位監(jiān)視、電源監(jiān)控繼電器HRTH
三合一繼電器使用條件
A.不得有雨水和雪,有防霧、防塵、防風沙設施。
B.周圍磁場強度:小于0.5mT;
C.工作位置:任意;
D.工作電壓:不大于120%額定電壓;
E).無導電氣體,無腐蝕性氣體,無較強振動;
F.環(huán)境溫度:-10℃~50℃;
HRTH-Y-2H2D;HRTH-J-2H2D-X三合一繼電器用途
HRTH-Y-2H2D;HRTH-J-2H2D-X三合一繼電器用于直流或交流操作的各種自動控制或保護線路中,可以直接控制分閘、合閘回路,監(jiān)視控制電源,并方便調節(jié)合閘回路 和電源監(jiān)視回路出口中間繼電器斷電返回的延時時間。
HRTH-Y-2H2D;HRTH-J-2H2D-X三合一繼電器技術參數
(1).額定值:220VDC、110VDC、48VDC、380VAC、220VAC、110VAC。
(2).動作值:直流電壓不大于70%額定值,交流電壓不大于80%額定值。
(3).返回值:不小于10%額定值。
(4).動作時間:施加額定電壓,動作時間小于20ms。
(5).返回時間:分閘回路小于20ms,合閘回路20ms~3s可調,電源監(jiān)視回路20ms~3s可調。
(6).功 耗:整體功耗小于10W。
(7).觸點容量:可長期接通5A,在250VDC τ=5ms條件,大可斷開50W直流有感負載;
在250VAC COSΦ=0.4大可斷開250VA交流負載。
(8).絕緣電阻:外殼與外露帶電端子之間,用開路電壓500V的兆歐表測量,絕緣電阻大于300MΩ。
(9).介質強度:外殼與外露帶電端子之間,能承受2KV(有效值)50Hz試驗電壓,歷時1分鐘不擊穿,無閃絡。