- Short circuit loop resistance measurement:
- short circuit loop phase-to-phase(L-L) and phase-to-PE(N) measurement, neutral L-PE(N),
- automatic calculation of prospective short-circuit loop current,
- selectable test leads length 1,2m; 5m; 10m; 20m, - Test for coutinuity of protecting wires and equalizing connection.
- AC voltages measurement.
- Autoranging.
- Memory of the last measurement.
- AUTO-OFF function.
- Versions available:
- MZC-200: operate in mains voltage 220/380 V or 230/400 V,
- MZC-201: operate in mains voltage 290/500 V,
- MZC-202: operate in mains voltage 100/170 V,
- MZC-203: instrument, manufactured at special order for any chosen mains voltages, less than 500V, allows short circuit loop impedance measurement.
- Meter meets the requirements of the standard EN 61557.
The range of voltages in the short circuit loop resistance measurement:
- MZC-200: 180...440V
- MZC-201: 240...550V
- MZC-202: 85...190V
- MZC-203: upon request, up to 500V
rated frequency: 45...65 Hz
Short-circuit loop measurement resistor:
- MZC-200: 15 Ω
- MZC-201: 22 Ω
- MZC-202: 6,8 Ω
- MZC-203: selected according to the rated voltage
- MZC-200
for 230V: 15,3A (10ms)
for 400V: 26,7A (10ms) - MZC-201
for 290V: 13,2A (10ms)
for 500V: 22,7A (10ms) - MZC-202
for 100V: 14,7A (10ms)
for 170V: 25,0A (10ms) - MZC-203
selected according to the rated voltage
Short circuit loop resistance measurement:
measuring range according to IEC 61557 for voltages196...440V, and a phases angle 0...180°
and 1,2m long test leads: 0,24...200Ω
Range | Resolution | Accuracy |
0,00...9,99Ω | 0,01 Ω | ±(2,5% m.v. + 5 digits) |
10,0...99,9Ω | 0,1 Ω | ±(2,5% m.v. + 3 digits) |
100...200Ω | 1 Ω | ±(3% m.v. + 3 digits) |
AC voltages measurement
Meter type | Range | Resolution | Accuracy |
MZC-200 | 0...440 V | 1 V | ±(2% m.v. + 2 digits) |
MZC-201 | 0...550 V | ||
MZC-202 | 0...250 V | ||
MZC-203 | (max. 500 V) |
?frequency 45...65Hz
Prospective of the short circuit loop current (calculated Rs and Un)
Range | Resolution | Accuracy |
0...9,99A | 0,01A | accuracy of the current indication computed, respectively, with the use of resistance measurement |
10,0...99,9A | 0,1A | |
100...999A | 1A | |
1,00...9,99kA | 0,01kA | |
10,0 ... ***kA | 0,1kA |
Meter type | for UL-N | for UL-L |
MZC-200 | 23,0 kA | 40,0 kA |
MZC-201 | 29,0 kA | 50,0 kA |
MZC-202 | 10,0 kA | 17,0 kA |
MZC-203 | upon request |
„m.v.” - measured value